Connecting AC Power (ICC-801PL and ICC-800M/ICC-800SS)

  1. Remove the cover from junction box.
  2. Strip 1/2" off of each wire.
  3. For all connections, route the wires through the conduit opening inside the junction box.
  4. For 120 volt connections see Figure 3. For 230 volt connections see Figure 4.
  5. Replace faceplate of junction box and screw into place.

Grounding the ICC

The ICC is equipped with built-in electrical surge protection. For this system to function properly, the earth ground terminal on the power module must be connected to a ground rod that is driven into the earth.

Important: Use a #10 (6 mm) or #8 (10 mm) bare wire to connect the controller to the ground rod. Use a standard copper clad, 5/8" (1.6 cm) diameter, 8' (2.5 m) long ground rod.

To connect ground wire:

Feed the ground wire up through the large hole at the bottom of the controller cabinet (the same hole used for the valve wires).

Loosen the screw on the GND terminal on the power module and place the ground wire into the terminal. Tighten the screw so that the ground wire is secure (see Figure 5).