Troubleshooting Guide

PROBLEM

CAUSES

SOLUTIONS

There is no display. Check AC power wiring. Correct any errors.
The display reads “ERR” Electrical noise is entering the system. Check the SmartPort® wiring harness. If the wires were extended then they will need to be replaced with shielded cable. Contact your local distributor for information on shielded cable.

The display reads “P ERR”.

There is a ground fault in the wire to the pump start or master valve. Check the master valve or pump start wire for continuity. Replace or repair the broken wire. Check that all wire connections are good and water tight.
The display reads a station number and ERR, such as “2 ERR”. There is a ground fault in the wire leading to that station. Check the station wire for continuity. Replace or repair broken wire. Check that all wire connections are good and water tight.
The display reads “NO AC”. There is no AC power present to operate controller/valves. Check to see if the transformer is properly installed.
The display reads “SEN OFF”. The rain sensor is interrupting irrigation or not installed. Slide the Rain Sensor switch on front panel to the bypass position to bypass rain sensor circuit.
The Controller does not start automatically Potential user programming error. Check to make sure start time is entered correctly (note AM/PM setting as well). Check to make sure watering day is active.
Rain sensor will not shut off system. Incorrect sensor type wired directly into sensor circuit. Make sure sensor is microswitch type such as Mini-Clik®.
The controller recognizes 48 stations all the time. Microprocessor requires reset. Make sure AC power is connected. Reset controller using method described here.
The controller does not respond to all the stations. Example, the controller has 24 stations but the display will only go to 16 stations. Controller does not recognize modules. Turn off the power to the controller and remove the battery. Check all module connections to the controller. Power the controller back up. The microprocessor will recognize all modules.
The controller is only recognizing eight stations when multiple modules are installed and/or there are not enough start times for all stations. User programming error. User is checking start times, not station run times. Be sure dial is in correct position. Total number of stations can be easily checked by placing dial in SET STATION RUN TIMES position and pressing the back arrow.
Controller has display but will not activate zone valves. Primary power to controller incorrectly wired. Controller receiving voltage too low for valve operation. Check and correct 110 or 220 volt connection. 110 volt may be incorrectly wired as 220 volt.
The controller is continuously watering even when it should not be on/controller cycles over and over. Too many start times (user programming error). Only one start time per active program is required. Refer to "Setting Watering Start Times".