Proper installation and connection of the decoder two-wire paths is very important. Learn more
- Use only Hunter IDWIRE or an approved substitute.
- Use only Hunter DBRY-6 waterproof connectors in the red and blue two-wire path connections.
- Leave adequate slack (about 5' or 1.5 m) at each splice to prevent disconnection.
Each A2C-D75 output module supports up to 75 decoder stations.
- Each module allows up to three two-wire path connections.
- Each path may be up to 10,000' (3 km) with 14 AWG (2 mm2) wire or up to 15,000' (4.5 km) with 12 AWG (approximately 3.31 mm2) wire.
- Two-wire paths may be tee-spliced (in a valve box with approved connectors) as long as the maximum distance to each end of the paths from the controller does not exceed the maximum for the wire used.
You can have more than 75 stations on a single two-wire path. If more than one A2C-D75 is installed, it is possible to assign the additional station numbers to another decoder output module. This must be done with the Station Assignments function on the Decoder menu so the controller will know which module has the additional stations. Learn more
Station Decoders
Model | Input Wire | Station Output #1 | Station Output #2 | Station Output #3 | Station Output #4 | Station Output #5 | Station Output #6 |
---|---|---|---|---|---|---|---|
ICD-100 | Red/Blue | Black/Black | N/A | N/A | N/A | N/A | N/A |
ICD-200 | Red/Blue | Black/Black | Yellow/Yellow | N/A | N/A | N/A | N/A |
ICD-400 | Red/Blue | Black/Black | Yellow/Yellow | Green/Green | White/White | N/A | N/A |
ICD-600 | Red/Blue | Black/Black | Yellow/Yellow | Green/Green | White/White | Orange/Orange | Purple/Purple |
Sensor Decoder
Model | Input Wire | Sensor Type | Wires | Compatible Sensors |
---|---|---|---|---|
ICD-SEN | Red/Blue | Port - A (+ -) | Purple/White | Flow Sensor Only |
Red/Blue | Port - B (+ -) | Orange/White | Clik Sensor(s) |