ACC2 - Station Setup

Allows stations to be named. Most other functions are described in more detail in the Flow Operations section.

Station P/MV Usage indicates which normally-closed P/MV outputs the station will activate, whenever it runs.

Station Flow Zone assignment (required for Flow Manager and/or Flow Monitoring).

Flow Priority (used in Flow Manager). Check the box to make a station more likely to water earlier in flow management.

Flow Rate: Enter or learn the typical flow for the station. Used in both Flow Manager and Flow Monitor. See Flow Operations.

Delay: Sets the amount of time the station can run before high or low flows will cause an alarm. Set longer delays for stations that take longer to stabilize flow.

P/MV boxes with the “X” are unavailable, because they are already assigned to other Flow Zones or MainSafe zones.