A Hunter weather sensor or other micro-switch-type weather sensors can be connected to the Pro-C® Controller. The purpose of this sensor is to stop automatic watering when weather conditions dictate.
- Remove the metal jumper plate that is attached across SEN-2 and COM.
- Connect one wire from the sensor to the SEN-2 screw terminal and the other sensor wire to the COM terminal. When the weather sensor has deactivated automatic watering, OFF will appear on the display.
IMPORTANT: The SEN-1 terminal will only be used for the Solar Sync Sensor. Learn More
Pro-C Model Sensor Wiring Comparison Chart

IMPORTANT: The Manual single-station function ignores any attached sensor and will allow watering.

Pro-C Model |
Wiring Diagram |
---|
PC-400 (3rd Generation)

|
- Route the wires from the rain sensor up through the same conduit used for valve wiring.
- Remove the flat jumper from the two SEN terminals.
- Connect one wire to the SEN terminal and one to the other SEN terminal.

|
PC-300 (2nd Generation)

|
- Route the wires from the rain sensor up through the same conduit used for valve wiring.
- Remove the flat jumper from the two SEN terminals.
- Connect one wire to the SEN terminal and one to the other SEN terminal.

|
PC-300 (Original Version)

|
- Route the wires from the rain sensor up through the same conduit used for valve wiring.
- Remove the flat jumper from the two SEN terminals.
- Connect one wire to the SEN terminal and one to the other SEN terminal.

|