Flow-Sync not reading
Cause
- Water shut off
- Controller not configured
- Faulty Wiring- Use voltmeter to verify red and black wires are connected, and have not been reversed.
- Damaged sensor- Impeller damage (debris in water) or Flow-Sync electronics damage (lightning)
Solution
- Verify that no isolation valves are closed, and that the water source is on.
- Check controller flow sensor setup. Enter sensor size (and location, for sensor decoders) and other sensor information as required.
- Fix any wire splices. Correct polarity (red and black).
- Replace sensor.
Flow-Sync not reading correctly
Cause
- Controller configured incorrectly
- Turbulent flow at sensor
Solution
- Set correct flow sensor size and type at controller.
- Insure that straight pipe is on either side of flow meter.
Frequent false alarms
Cause
- Station settings too sensitive
- Wide range of flows for a single station
Solution
- Increase overflow percentage (and underflow if available).
- Increase overflow and underflow percentages, and delay interval.